  the e-series hydraulic/magnetic circuit breaker is ideally suited for higher current and voltage applications. it is ul listed and csa certifed for branch circuit protection, which does not require a fuse back up. it is also ul recognized and csa certifed as a supplementary protector and as a manual motor controller. its physical features include front and back mounting, screw and stud terminals and heavy duty box wire connectors for solid wire or a pressure plate connector for standard wire. the e-series is available with handle actuators and can be confgured as .1-125 amps, up to 600vac or 125vdc, with choice of time delays, actuator colors and 1 to 6 poles confguration. additionally, a power selector device is also available. product highlights: ? ul listed and csa certifed ? certifed for circuit branch protection ? recognized as a supplementary protector and as a manual motor controller ? optional power selector device typical applications: ? ideal for higher current and voltage applications ? renewable energy systems ? military ? industrial controls ? generators e-series circuit breaker carling technologies, inc. 60 johnson avenue ? plainville, ct 06062-1177 phone: (860) 793-9281 ? fax: (860) 793-9231 email: sales@carlingtech.com ? www.carlingtech.com
2 | e-series circuit breaker - general specifcations maximum voltage current ratings auxiliary switch rating insulation resistance dielectric strength resistance, impedance pulse tolerance curves environmental physical mechanical electrical designed in accordance with requirements of specifcation mil prf-55629 & mil-std-202g as follows: shock vibration moisture resistance salt spray thermal shock operating temperature number of poles mounting connectors, box type internal circuit confguration weight standard colors endurance trip free trip indication 600vac 50/60 hz, 125vdc (table a) standard current coils: 0.100, 0.250, 0.500, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0, 20.0, 25.0, 30.0, 50.0, 60.0, 70.0, 100 & 125 amp. spdt; 10.1a 250vac, 1.0a 65vdc; 0.5a 80vdc, 0.1a 125vac (with gold contacts). minimum of 100 megohms at 500 vdc. ul, csa: 2200 v 50/60 hz for one minute between all electrically isolated terminals. e-series circuit breakers comply with the 8mm spacing and 3750v 50/60 hz dielectric requirements from hazardous voltage to operator accessible surfaces, between adjacent poles and from main circuits to auxiliary circuits per publications en 60950 and vde 0805. values from line to load terminal - based on series trip circuit breaker. withstands 100 gs, 6ms, sawtooth while carrying rated current per method 213, test condition i. withstands 0.060 excursion from 10-55 hz, and 10 gs 55-500 hz, at rated current per method 204c, test condition a. method 106d, i.e., ten 24-hour cycles @ + 25c to +65c, 80-98% rh. method 101, condition a (90-95% rh @ 5% nacl solution, 96 hrs). method 107d, condition a (five cycles @ -55c to +25c to +85c to +25c). -40 c to +85 c 1 - 6 a 3 minimum spacing must be provided between the circuit breaker arc venting area on back connected e-series circuit breakers and grounded obstructions. e-series circuit breakers must be mounted on a vertical surface. front connected e-series circuit breakers are supplied with box type pressure connectors that accept copper or aluminum conductors as follows: 1/0-14 copper, 1/0-12 aluminum. series and switch only, (with or without auxiliary switch). shunt with current coils. approximately 252 grams/pole (approximately 9 ounces/pole) housing-black; actuator - see ordering scheme. 6,000 on-off operations @ 6 per minute; with rated current and voltage. additional 4,000 on-off mechanical. all e-series circuit breakers will trip on overload, even when handle is forcibly held in the on position. the operating handle moves positively to the off position when an overload causes the breaker to trip. *manufacturer reserves the right to change product specification without prior notice. 60 johnson avenue ? plainville, ct 06062C1177 ? phone: (860) 793C9281 ? fax: (860) 793C9231 email: sales @ carlingtech.com ? www.carlingtech.com
| 3 e-series circuit breaker - general specifcations electrical tables table a: lists ul listed (489) & csa certifed (c22.2 no. 5) confgurations & performance capabilities as a molded case circuit breaker. table b: lists ul recognized & csa accepted confgurations & performance capabilities as a component supplementary protector. 80 dc --- 0.10 - 100 5,000 50,000 125 dc --- 0.10 - 100 5,000 10,000 125 dc --- 101 - 125 10,000 --- 120 50 / 60 1 101 - 125 10,000 --- series 240 50 / 60 10 .10 - 30 5,000 10,000 240 50 / 60 1 31 - 100 5,000 120 / 240 50 / 60 10 .10 - 30 5,000 10,000 120 / 240 50 / 60 1 31 - 100 5,000 --- 120 / 240 50 / 60 1 101 - 125 10,000 --- 240 50 / 60 30 .10 - 100 5,000 --- e series ta ble a : ul489 listed branch circuit breakers voltage interrupting capa city (amps) max. ra ting frequency phase without backup fuse circuit configura tion full load amps current ra ting high interrupting capa city (amps) 125 dc --- 0.02 - 100 --- --- 5,000 tc1,2, ol1, u1 tc1,2, ol1, u1 125 dc --- --- 101 - 120 --- 5,000 tc1,2, ol0, u1 tc1,2, ol0, u1 150 dc --- --- 0.02 - 125 --- 5,000 tc1, ol0, u3 tc1, ol0, u3 160 dc --- 0.02 - 100 --- --- 5,000 tc1,2, ol1, u1 tc1,2, ol1, u1 150 / 300 dc --- 0.02 - 100 --- --- 5,000 tc1,2, ol1, u1 tc1,2, ol1, u1 series & 120 / 240 50 / 60 1 --- 0.02 - 100 --- 5,000 tc1,2, ol0, u1 tc1,2, ol0, u1 shunt 240 50 / 60 1 0.02 - 100 --- --- 5,000 tc1,2, ol1, u1 tc1,2, ol1, u1 250 50 / 60 1 0.02 - 100 --- 10,000 --- tc1,2, ol1, c1 tc1,2, ol1, c1 --- 5,000 tc1,2, ol1, u1 tc1,2, ol1, u1 10,000 --- tc1,2, ol1, c1 tc1,2, ol1, c1 480 50 / 60 1 & 3 0.02 - 100 --- 10,000 --- tc1,2, ol1, c1 tc1,2, ol1, c1 480 1 50 / 60 1 & 3 0.02 - 50 --- 10,000 --- tc1,2, ol1, c1 tc1,2, ol1, c1 600 50 / 60 1 & 3 0.02 - 100 --- 10,000 --- tc1,2, ol1, c1 tc1,2, ol1, c1 600 2 dc --- --- 0.02 - 125 --- 5,000 tc1, ol0, u3 tc1, ol0, u3 125 dc --- 0.02 - 120 160 dc --- 0.02 - 100 switch 240 50 / 60 1 0.02 - 100 only 277 50 / 60 1 0.02 - 100 480 50 / 60 1 & 3 0.02 - 100 600 50 / 60 1 & 3 0.02 - 100 277 50 / 60 1 0.02 - 100 --- csa with backup fuse 3 without backup fuse e -series t able b: component supplementa ry protecto rs circuit configura tion voltage current ra ting shor t circui t capa city (amps) applica tion codes max. ra ting frequency phase full load amps general purpose amps ul/csa ul table b notes: 1 per pole opposite polarity rating - delta confguration. 2 4 poles connected in series 3 requires branch circuit backup with a ul listed type k5 or rk5 fuse rated 15a minimum and no more than 4 times full load amp rating and not to exceed 225a. agency certifications ul recognized ul standard 1077 ul standard 1500 ul listed ul standard 489 csa accepted csa certifed tuv certifed vde certifed component recognition program as protectors, supplementary (guide qvnu2, file e75596) component recognition program as manual motor controls (guide nlrv2, file e135367) protectors, supplementary for marine electrical & fuel systems (guide peqz2, file e75596) ignition protection circuit breakers, molded case (guide divq, file e129899) component supplementary protector (class 3215 30, file 047848 0 000) csa standard c22.2 no. 235 circuit breaker molded case (class 1432 01, file 093910), csa standard c22.2 no. 5.1 - m en60934 under license no. r72031056 en60934, vde 0642 under file no. 10537 60 johnson avenue ? plainville, ct 06062C1177 ? phone: (860) 793C9281 ? fax: (860) 793C9231 email: sales @ carlingtech.com ? www.carlingtech.com 60 johnson avenue ? plainville, ct 06062C1177 ? phone: (860) 793C9281 ? fax: (860) 793C9231 email: sales @ carlingtech.com ? www.carlingtech.com
4 | e-series circuit breaker - general specifcations table c: lists ul recognized, csa accepted and vde certifed confgurations and performance capabilities as a component supplementary protector. table d: lists ul recognized, csa accepted confgurations and performance capabilities as protectors, supplementary for marine electrical and fuel systems (guide peqz2, file e75596). ignition protected per ul 1500. ul classifed small craft electrical devices, marine in accordance with iso 8846 (guide uzmk, file mq1515) as marine supplementary protectors. curren t ra ting vde (icn) construction notes 125 dc --- 0.1 - 100 --- 5,000 5,000 tc1,2, ol1, u1 tc1,2, ol1, u1 1 or 2 poles series & 240 50 / 60 1 & 30 .1 - 100 --- 5,000 5,000 tc1,2, ol1, u1 tc1,2, ol1, u1 1 - 5 poles. up to 4 current poles, 1 v oltage pole shunt 415 50 / 60 1 & 30 .1 - 100 10,000 --- 4,000 tc1,2, ol1, c1 tc1,2, ol1, c1 2 - 5 poles. up to 4 current poles, 1 v oltage pole 125d c --- 0.1 - 125 switch only 240 50 / 60 1 & 30 .1 - 100 415 50 / 60 1 & 30 .1 - 100 e -series ta ble c: component supplementa ry protect ors with vde shor t circuit capa city (amps) without backup fuse ul/csa ul csa with backup fuse 1 without backup fuse circui t configura tion voltage applicat ion codes max. ra ting frequency phase full load amps 65 dc --- 0.02 - 1005 ,000 tc1,2,ol1,u1 tc1,2,ol1,u1 series 125 50 / 60 1 0.02 - 1001 ,500 tc1,2,ol1,u1 tc1,2,ol1,u1 250 50 / 60 1 0.02 - 1001 ,500 tc1,2,ol1,u1 tc1,2,ol1,u1 without backup fuse ul applicat ion codes e series t able d : ul1500 (marine ignition protection ) csa circuit configura tio n voltage curren t ra ting shor t circuit cap acity (amps) max. ra ting frequency phase full load amps electrical tables table c notes: 1 requires branch circuit backup with a ul listed type k5 or rk5 fuse rated 15a minimum and no more than 4 times full load amp rating and not to exceed 225 amps. 60 johnson avenue ? plainville, ct 06062C1177 ? phone: (860) 793C9281 ? fax: (860) 793C9231 email: sales @ carlingtech.com ? www.carlingtech.com
| 5 e-series handle ul recognized C ordering scheme 7 current rating (amperes) 7 or voltage coil (min. trip rating, volts) 5 020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 090 0.095 210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 35.000 640 40.000 650 50.000 660 60.000 670 70.000 680 80.000 690 90.000 810 100.000 811 110.000 812 120.000 912 8 125.000 code amperes a06 6 dc, 5 dc a12 12 dc, 10 dc a18 18 dc, 15 dc a24 24 dc, 20 dc a32 32 dc, 25 dc a48 48 dc, 40 dc a65 65 dc, 55 dc b25 125 dc, 100 dc j06 6 ac, 5 ac j12 12 ac, 10 ac j18 18 ac, 15 ac j24 24 ac, 20 ac j48 48 ac, 40 ac j65 65 ac, 55 ac k20 120 ac, 65 ac l40 240 ac, 130 ac C C C C C 1 series 2 actuator 3 poles 6 frequency & delay 7 current rating 8 terminal 12 agency approval 4 circuit 5 auxiliary switch e a b 0 1 a 2 2 b c 24 450 1 series e 2 actuator a handle, one per pole 8 terminal 12 back connected (front mounted only) max. rating 1 9 10-32 stud (all terminals) 50 a 2 9 1/4-20 stud (all terminals) 120 a a 9 m5 stud (line & load) 50 a b 9 m6 stud (line & load) 100 a front connected (back mounted only) max. rating 3 10 box wire connector (line & load) 100 a c 11 box wire connector w/ pressure plate (line & load) 100 a 4 10-32 screw (line & load) 50 a d m5 screw (line & load) 50 a 5 10-32 bus-type screw (line), 10-32 screw (load) 50 a e m5 bus-type screw (line), 10-32 screw (load) 50 a 6 10 10-32 bus-type screw (line), box wire connector (load) 100 a f 11 10-32 bus-type screw (line), box wire connector w/ pressure plate (load) 100 a 7 1/4-20 screw (line & load) 100 a g m6 screw (line & load) 100 a 8 1/4-20 bus-type screw (line), 1/4-20 screw (load) 100 a h m6 bus-type screw (line), m6 screw (load) 100 a 9 10 1/4-20 bus-type screw (line), box wire connector (load) 100 a j 11 1/4-20 bus-type screw (line), box wire connector w/ pressure plate (load) 100 a 10 mounting/barriers back connected (front mounted only) mounting inserts a 6-32 b iso m3 front connected (back mounted only) 14 back mounting foot type front mounting inserts (optional use) c short 6-32 d short iso m3 e long 6-32 f long iso m3 3 poles 1 1 one 2 two 3 three 4 four 5 five 6 six 4 circuit 2 a 3 switch only ( no coil ) b series trip ( current ) c series trip ( voltage ) d shunt trip ( current ) e shunt trip ( voltage ) f relay trip ( current ) g relay trip ( voltage ) 5 auxiliary switch 4 0 without auxiliary switch 2 s.p.d.t. 0.110 q.c. terminals 3 s.p.d.t. 0.139 solder lug 4 s.p.d.t. 0.110 q.c. terminals (gold contacts) 6 s.p.d.t. 0.110 q.c. terminals 7 s.p.d.t. 0.110 q.c. terminals (gold contacts) 8 s.p.d.t. 0.187 q.c. terminals 9 s.p.d.t. 0.187 q.c. terminals 6 frequency & delay 03 3 dc 50/60hz, switch only 10 5 dc instantaneous 12 dc short 14 dc medium 16 dc long 20 5 50/60hz instantaneous 22 50/60hz short 24 50/60hz medium 26 50/60hz long 30 dc, 50/60hz instantaneous 32 dc, 50/60hz short 34 dc, 50/60hz medium 36 dc, 50/60hz long 62 50/60hz short, hi-inrush 64 50/60hz medium, hi-inrush 66 50/60hz long, hi-inrush 72 dc, short,hi-inrush 74 dc,medium, hi-inrush 76 dc, long, hi-inrush 92 6 dc, 50/60hz short, hi-inrush 94 6 dc, 50/60hz medium, hi-inrush 96 6 dc, 50/60hz long, hi-inrush 11 maximum application rating 15 12 agency approval b d ul 1077 / ul508 recognized & csa accepted ul 1077 recognized, csa accepted, & vde certifed 9 actuator color 10 mounting/ barriers 11 maximum application rating 9 actuator color & legend 13 acuator color white black red green blue yellow gray orange legend color black white white white white black black black i-o a c f h k m p r on-off b d g j l n q s dual 1 2 3 4 5 6 7 8 a 65 vdc, 120 a b 125 vdc, 120 a c 120/240 vac, 100 a d 240 vac, 100 a e 16 277/480 vac, 100 a f 277 vac, 100 a g 16 600 vac, 100 a h 16 480 vac, 100 a j 16 415 vac, 100 a l 16 160 vdc, 100 a t 125 vdc/240 vac, 100 a w 16 125 vdc/415 vac, 100 a notes: 1 vde approval on 1-5 poles only. standard multi-pole units identical poles except when specifying auxiliary switch - (see note 4). for mixed ratings, consult factory. 2 switch only & series trip construction available w/either front or back connected terminals. shunt construction available w/back connected terminals, (terminal codes 1 & 2) only. circuit codes b,c & d are vde approved. 3 switch only construction: 30 amps or less select current rating code 630; 31-70 amps, select current rating code 670; 71-100 amps, select current rating code 810; 101-125 amps select current rating code 912. switch only is vde approved only if tied to a protected pole. 4 auxiliary switch available on switch only and series trip units. on multi-pole units, only one auxiliary switch is normally supplied mounted in the extreme right pole. back mounted units require special mounting provisions when auxiliary switch is specifed. vde approval on auxilary switch codes 0,2,3 & 4 only. 5 voltage trip coils are not rated for continuous duty. available only with frequency & delay codes 10 & 20. series trip construction with a voltage coil s vde approved only if tied to a protected pole. 6 frequency & delay codes 92,94 & 96 are not vde certifed. 7 current coil ratings 0.100 - 100 ams are vde certifed. 8 125 a rating (code 912) available as a switch only (circuit code a), rated 125 vdc (code b). 9 an anti-flash over barrier is supplied between poles on multi-pole units with 10-32 (terminal code 1). 1/4-20 (code 2), m5 (code a), and m6 (code b) terminals per ul requirement. 10 box wire connector will accept #14 through 0 awg. copper wire or #12 through 0 awg. aluminum wire. 11 box wire connector with pressure plate for stranded wire, consult factory for details. 12 terminal codes a,b,d,e,g & h are not vde certifed. 13 vde approvals require dual (i-o, on-off) or i-o markings on all handles. 14 back mounted breakers can also be front mounted by utilizing the proper front panel mounting inserts normally supplied. however, terminal connections must be made prior to mounting. 15 application ratings b,d,j,t & w are available with vde. 16 415, 480 & 600 vac ratings require 3 or 4 pole break 3? and 2 pole break 1?. 60 johnson avenue ? plainville, ct 06062C1177 ? phone: (860) 793C9281 ? fax: (860) 793C9231 email: sales @ carlingtech.com ? www.carlingtech.com 60 johnson avenue ? plainville, ct 06062C1177 ? phone: (860) 793C9281 ? fax: (860) 793C9231 email: sales @ carlingtech.com ? www.carlingtech.com
6 | e-series handle ul listed C ordering scheme 7 current rating (amperes) 7 or voltage coil (min. trip rating, volts) 5 020 0.020 025 0.025 030 0.030 035 0.035 040 0.040 045 0.045 050 0.050 055 0.055 060 0.060 065 0.065 070 0.070 075 0.075 080 0.080 085 0.085 090 0.090 090 0.095 210 0.100 215 0.150 220 0.200 225 0.250 230 0.300 235 0.350 240 0.400 245 0.450 250 0.500 255 0.550 260 0.600 265 0.650 270 0.700 275 0.750 280 0.800 285 0.850 290 0.900 295 0.950 410 1.000 512 1.250 415 1.500 517 1.750 420 2.000 522 2.250 425 2.500 527 2.750 430 3.000 435 3.500 440 4.000 445 4.500 450 5.000 455 5.500 460 6.000 465 6.500 470 7.000 475 7.500 480 8.000 485 8.500 490 9.000 495 9.500 610 10.000 710 10.500 611 11.000 711 11.500 612 12.000 712 12.500 613 13.000 614 14.000 615 15.000 616 16.000 617 17.000 618 18.000 620 20.000 622 22.000 624 24.000 625 25.000 630 30.000 635 35.000 640 40.000 650 50.000 660 60.000 670 70.000 680 80.000 690 90.000 810 100.000 811 110.000 812 120.000 912 8 125.000 code amperes a06 6 dc, 5 dc a12 12 dc, 10 dc a18 18 dc, 15 dc a24 24 dc, 20 dc a32 32 dc, 25 dc a48 48 dc, 40 dc a65 65 dc, 55 dc b25 125 dc, 100 dc j06 6 ac, 5 ac j12 12 ac, 10 ac j18 18 ac, 15 ac j24 24 ac, 20 ac j48 48 ac, 40 ac j65 65 ac, 55 ac k20 120 ac, 65 ac l40 240 ac, 130 ac C C C C C 1 series 2 actuator 3 poles 6 frequency & delay 7 current rating 8 terminal 12 agency approval 4 circuit 5 auxiliary switch e a b 0 1 a 2 2 c c 24 450 1 series e 2 actuator a handle, one per pole 8 terminal 7 back connected (front mounted only) max. rating 1 8 10-32 stud (all terminals) 50 a 2 8 1/4-20 stud (all terminals) 125 a front connected (back mounted only) max. rating 3 9 box wire connector (line & load) 100 a c 10 box wire connector w/ pressure plate (line & load) 100 a 4 10-32 screw (line & load) 50 a 5 10-32 bus-type screw (line), 10-32 screw (load) 50 a 6 9 10-32 bus-type screw (line), box wire connector (load) 100 a f 10 10-32 bus-type screw (line), box wire connector w/ pressure plate (load) 100 a 7 1/4-20 screw (line & load) 125 a 8 1/4-20 bus-type screw (line), 1/4-20 screw (load) 100 a 9 9 1/4-20 bus-type screw (line), box wire connector (load) 100 a j 10 1/4-20 bus-type screw (line), box wire connector w/ pressure plate (load) 100 a 10 mounting/barriers back connected (front mounted only) mounting inserts a 6-32 b iso m3 front connected (back mounted only) 11 back mounting foot type front mounting inserts (optional use) c short 6-32 d short iso m3 e long 6-32 f long iso m3 3 poles 1 1 one 2 two 3 three 4 four 5 five 6 six 4 circuit 2 b series trip ( current ) c 3 series trip ( voltage ) 5 auxiliary switch 4 0 without auxiliary switch 2 s.p.d.t. 0.110 q.c. terminals 3 s.p.d.t. 0.139 solder lug 4 s.p.d.t. 0.110 q.c. terminals (gold contacts) 6 s.p.d.t. 0.110 q.c. terminals 7 s.p.d.t. 0.110 q.c. terminals (gold contacts) 8 s.p.d.t. 0.187 q.c. terminals 9 s.p.d.t. 0.187 q.c. terminals 6 frequency & delay 10 5 dc instantaneous 12 dc short 14 dc medium 16 dc long 20 5 50/60hz instantaneous 22 50/60hz short 24 50/60hz medium 26 50/60hz long 30 dc, 50/60hz instantaneous 32 dc, 50/60hz short 34 dc, 50/60hz medium 36 dc, 50/60hz long 62 50/60hz short, hi-inrush 64 50/60hz medium, hi-inrush 66 50/60hz long, hi-inrush 72 dc, short,hi-inrush 74 dc,medium, hi-inrush 76 dc, long, hi-inrush 92 6 dc, 50/60hz short, hi-inrush 94 6 dc, 50/60hz medium, hi-inrush 96 6 dc, 50/60hz long, hi-inrush 11 maximum application rating 12 agency approval c f ul 489 listed & csa certifed ul 489 listed, csa certifed, & vde certifed 9 actuator color 10 mounting/ barriers 11 maximum application rating 9 actuator color & legend 12 acuator color white black red green blue yellow gray orange legend color black white white white white black black black on-off b d g j l n q s dual 1 2 3 4 5 6 7 8 1 120 vac b 125 vdc, 120 a c 13 120/240 vac, 100 a d 240 vac, 100 a notes: 1 standard multi-pole units identical poles except when specifying auxiliary switch - (see note 4). for mixed ratings, consult factory. vde certifcation on 1-5 poles only. 2 series trip construction available w/either front or back connected terminals. 3 series trip construction with a voltage coil is not available as a single pole unit and must be tied to a protected pole. 4 on multi-pole units, only one auxiliary switch is normally supplied mounted in the extreme right pole per figure a. back mounted units require special mounting provisions when auxiliary switch is specifed. vde certifcation on auxilary swit ch codes 0, 2, 3 & 4 only. 5 voltage trip coils are not rated for continuous duty. available only with frequency & delay codes 10 & 20. 6 frequency & delay codes 92, 94 & 96 are not vde certifed. 7 current ratings under 0.100 amps are not vde certifed . 8 an anti-flash over barrier is supplied between poles on multi-pole units with 10-32 stud (terminal code 1) or 1/4-20 stud (code 2) terminals per ul requirement. 9 box wire connector will accept #14 through 0 awg. copper wire or #12 through 0 awg. aluminum wire. 10 box wire connector with pressure plate for stranded wire, consult factory for details. 11 back mounted breakers can also be front mounted by utilizing the proper front panel mouning inserts normally supplied. however, terminal connections must be made prior to mounting. 12 vde certifcation requires dual (i-o , on-off) markings on all handles. 13 not available with vde certifcation. 60 johnson avenue ? plainville, ct 06062C1177 ? phone: (860) 793C9281 ? fax: (860) 793C9231 email: sales @ carlingtech.com ? www.carlingtech.com
| 7 e-series handle C circuit & terminal diagrams notes: 1 all dimensions are in inches [millimeters]. 2 tolerance .020 [.51] unless otherwise specifed. 3 0-50 amps: 10-32 & m5 studs .625.062/15.881.574 long. 4 51-120 amps: 1/4-20 & m6 studs .750.062/19.051.574 long. 60 johnson avenue ? plainville, ct 06062C1177 ? phone: (860) 793C9281 ? fax: (860) 793C9231 email: sales @ carlingtech.com ? www.carlingtech.com 60 johnson avenue ? plainville, ct 06062C1177 ? phone: (860) 793C9281 ? fax: (860) 793C9231 email: sales @ carlingtech.com ? www.carlingtech.com
8 | e-series handle (back connected) C form & fit drawings notes: 1 1/4 -20 stud terminal in series trip circuit confguration shown. 2 a 3 min spacing must be provided between the circuit breaker arc venting area of back connected e-series circuit breaker and grounded obstructions. 3 all dimensions are in inches [millimeters]. 4 tolerance .020 [.51] unless otherwise specifed. 5 circuit breakers must be mounted on vertical surface. 60 johnson avenue ? plainville, ct 06062C1177 ? phone: (860) 793C9281 ? fax: (860) 793C9231 email: sales @ carlingtech.com ? www.carlingtech.com
| 9 e-series handle (front connected) C form & fit drawings notes: 1 all dimensions are in inches [millimeters]. 2 tolerance .020 [.51] unless otherwise specifed. 3 box wire connector terminal in series trip circuit confguration shown. 4 circuit breakers must be mounted on vertical surface. rev_cb_e_0812 60 johnson avenue ? plainville, ct 06062C1177 ? phone: (860) 793C9281 ? fax: (860) 793C9231 email: sales @ carlingtech.com ? www.carlingtech.com 60 johnson avenue ? plainville, ct 06062C1177 ? phone: (860) 793C9281 ? fax: (860) 793C9231 email: sales @ carlingtech.com ? www.carlingtech.com


▲Up To Search▲   

 
Price & Availability of EA2-B0-24-450-12A-CB

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X